Room Details & Hazard Class
Calculation Preview
Room Volume (V)
240.00 m³Specific Volume (S)
0.1384 m³/kgRequired Conc.
7.5%FM-200 Agent Mass
1734.00 kg
What is FM-200?
FM-200 (Heptafluoropropane) is a clean agent fire suppression gas that is safe for occupied spaces. It suppresses fire by absorbing heat at the molecular level. It leaves no residue, making it ideal for protecting critical assets like server rooms and data centers.
NFPA 2001 Standard
This calculator is based on NFPA 2001, the Standard on Clean Agent Fire Extinguishing Systems. It calculates the required agent mass (W) using the formula: W = (V/S) * (C / (100-C)) * F, where V is Volume, S is Specific Volume, C is Concentration, and F is Safety Factor.
Disclaimer: This tool is for preliminary design purposes only. All calculations must be verified by a qualified fire protection engineer. FM-200® is a registered trademark of Chemours.